Download Product Brochure here https://www.erico.com/part.asp?part=TSG11302S
FEATURES
- Triggering air gap technology provides low let-through voltage, which offers superior protection compared to traditional spark gaps
- Effective equipotential bonding provides N-PE equalization protection bond on TT power distribution systems
- Can be used L-PE or L-N due to follow current control
SPECIFICATIONS
Part Number | TSG11302S |
Nominal System Voltage (Un) | 240 VAC |
Max Continuous Operating Voltage (Uc) | 440 VAC |
Voltage Protection Level (Up) | 1,500 V @ 3 kA 2,300 V @ 20 kA |
Max Discharge Current (Imax) | 130 kA 8/20 μs 50 kA 10/350 μs |
Follow Current Extinguishing Capability @ Un | 43 kA |
Impulse Current (Iimp) | 50 kA 10/350 μs |
Max Operating Current | 2.2 mA |
Protection Modes | Single |
Technology | Triggered Spark Gap |
Frequency | 50 – 60 Hz |
Enclosure Material | UL® 94V-0 Thermoplastic |
Enclosure Rating | IP 20 NEMA®-1 |
Mounting | 35 mm top hat DIN rail |
Status Indication | LED for line connected modes |
Temperature | -40 to 80 °C |
Module Width | 2 M |
Depth (D) | 68 mm |
Height (H) | 90 mm |
Width (W) | 36 mm |
Unit Weight | 0.3 kg |
Complies With | IEC® 61643-1 Class I, Class II ANSI®/IEEE® C62.41.2-2002 Cat A, Cat B, Cat C ANSI®/IEEE® C62.41.2-2002 Scenario II, Exposure 3, 100 kA 8/20 μs, 10 kA 10/350 μs |
Certifications | C-Tick |
Standard Packaging Quantity | 1 pc |
UPC | 78285647543 |
EAN-13 | 8711893132670 |
Reviews
There are no reviews yet.