Description
Download Product Brochure herehttps://www.erico.com/part.asp?part=TDS1301T150
FEATURES
- 20 kA 8/20 μs surge rating provides robust surge protection
- TD Technology with thermal disconnect protection
- Compact package, modular DIN rail mounting for limited space requirements
- Three modes of protection: L-N, L-PE and N-PE
- Indication flags and voltage-free contacts provide remote status monitoring
- Separate plug and base design facilitates replacement of a failed surge module
SPECIFICATIONS
Part Number | TDS1301T150 |
Nominal System Voltage (Un) | 120 – 150 VAC |
Max Continuous Operating Voltage (Uc) | 170 VAC |
Stand-off Voltage | 230 VAC |
Voltage Protection Rating (VPR) | 800 V @ 3 kA L-N 500 V @ 3 kA L+N-PE |
Nominal Discharge Current (In), Per Mode | 8 kA 8/20 μs |
Max Discharge Current (Imax) | 20 kA 8/20 μs L-N 20 kA 8/20 μs L-PE |
Back-Up Overcurrent Protection | 63 A |
Short Circuit Current Rating (SCCR) | 200 kA |
Frequency | 0 – 100 Hz |
Protection Modes | L-N L-PE N-PE |
Response Time | 5 ns Max |
Technology | TD technology with thermal disconnect |
Connection, PE Solid | 35 mm² Max |
Connection, PE Stranded | 25 mm² Max |
Connection, Solid | 6 mm² Max |
Connection, Stranded | 6 mm² Max |
Mounting | 35 mm top hat DIN rail |
Enclosure Material | UL® 94V-0 Thermoplastic |
Enclosure Rating | IP 20 NEMA®-1 |
Remote Contacts | No |
Status Indication | Mechanical flag |
Temperature | -40 to 80 °C |
Module Width | 1 M |
Depth (D) | 68 mm |
Height (H) | 90 mm |
Width (W) | 18 mm |
Unit Weight | 0.12 kg |
Certification Details | UL® 1449 Edition 3 Type 2, 3 kA Mode |
Complies With | ANSI®/IEEE® C62.41.2-2002 Cat A, Cat B IEC® 61643-1 Class III |
Replacement Module | TDS130M150 |
Certifications | UR |
Standard Packaging Quantity | 1 pc |
UPC | 78285662177 |
Reviews
There are no reviews yet.