Description
Download Product Brochure here https://www.erico.com/part.asp?part=DSD3100TNS275
FEATURES
- 100kA 8/20 us maximum surge rating per phase provides protection suitable for smaller, more compact main distribution panels and an extended operational life
- Indication flag provides clear visual indication of life status
- Remote contacts provide remote status monitoring
- Designed specifically for economical use within the Australian and New Zealand markets
SPECIFICATIONS
Part Number | DSD3100TNS275 |
Max Continuous Operating Voltage (Uc) | 275 VAC |
Max Discharge Current (Imax) | 100 kA 8/20 μs |
Nominal Discharge Current (In) | 40 kA 8/20 μs |
Voltage Protection Level (Up) | 800 V @ 3 kA |
Voltage Protection Level (Up) @ In | 1,600 V |
Impulse Current (Iimp) | 12.5 kA 10/350 μs |
Distribution System | TN-S |
Frequency | 0 – 60 Hz |
Protection Modes | L-N N-PE |
Short Circuit Current Rating (SCCR) | 25 kA |
Technology | MOV with thermal disconnect |
Connection, Solid | 35 mm² |
Connection, Stranded | 25 mm² |
Mounting | 35 mm top hat DIN rail |
Enclosure Material | UL® 94V-0 Thermoplastic |
Enclosure Rating | IP 20 |
Remote Contacts | Change-over contact (Form C dry) 250V~/0.5A, max 1.5 mm² |
Status Indication | Mechanical flag |
Terminal Torque | 3 N-m Max |
Temperature | -40 to 80 °C |
Depth (D) | 70 mm |
Height (H) | 90 mm |
Width (W) | 72 mm |
Unit Weight | 0.543 kg |
Complies With | ANSI®/IEEE® C62.41.2-2002 Cat A, Cat B, Cat C ANSI®/IEEE® C62.41.2-2002 Scenario II, Exposure 3, 100 kA 8/20 μs, 10 kA 10/350 μs AS/NZS1768 Cat B, Cat C AS/NZS3000 |
Standard Packaging Quantity | 1 pc |
UPC | 78285691412 |